Assessment Year | 1996 |
---|---|
Principal Product | Paper products and placemats |
NAICS |
n/a
|
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 86 |
Plant Area |
147,600
ft2
|
Annual Production | 8,500,000
pieces
|
Production Hrs. Annual | 3,945
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $65,744 | 2,238,277 |
kWh
|
$0.029 |
Electricity Demand | $76,624 | 8,362 |
kW-mo/yr
|
$9.16 |
Electricity Fees | $1,055 | - |
|
- |
Natural Gas | $36,583 | 4,856 |
MMBtu
|
$7.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $6,604 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,610 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $581 | $567 |
$116
3,810
kWh
|
$465
-
kW-mo/yr
|
- | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $426 | $906 |
$72
2,638
kWh
|
$354
-
kW-mo/yr
|
- | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $309 | $160 |
$309
10,844
kWh
|
- | - | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $967 | $330 |
$499
16,999
kWh
|
$468
-
kW-mo/yr
|
- | - | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $275 | $365 |
$275
9,379
kWh
|
- | - | - | - | |
06 | 2.4314: Use synthetic lubricant | $327 | $630 |
$327
11,137
kWh
|
- | - | - | - | |
07 | 2.2511: Insulate bare equipment | $65 | $26 |
$65
2,052
kWh
|
- | - | - | - | |
08 | 2.2437: Recover waste heat from equipment | $1,190 | $361 | - | - |
$1,190
-
MMBtu
|
- | - | |
09 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $2,464 | $7,000 | - | - | - | $(-1,286.0) | $3,750 | |
TOTAL RECOMMENDED | $6,604 | $10,345 |
$1,663
56,859
kWh
|
$1,287
-
kW-mo/yr
|
$1,190
-
MMBtu
|
$(-1,286.0) | $3,750 | ||
TOTAL IMPLEMENTED | $2,610 | $2,593 |
$1,323
45,428
kWh
|
$1,287
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs