| Assessment Year | 1996 |
|---|---|
| Principal Product | Metal, Glass & Ceramic Seals |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 200 |
| Plant Area |
70,545
ft2
|
| Annual Production | 6,000,000
pieces
|
| Production Hrs. Annual | 7,344
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $158,825 | 4,233,880 |
kWh
|
$0.038 |
| Electricity Demand | $44,353 | 8,417 |
kW-mo/yr
|
$5.27 |
| Electricity Fees | $11,377 | - |
|
- |
| Natural Gas | $9,683 | 1,470 |
MMBtu
|
$6.59 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $100,832 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $10,642 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,024 | $1,580 |
$1,698
36,342
kWh
|
$326
-
kW-mo/yr
|
- | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $327 | $160 |
$327
7,034
kWh
|
- | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $195 | $320 |
$195
4,103
kWh
|
- | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $825 | $300 |
$825
17,585
kWh
|
- | - | - | |
| 05 | 2.7241: Install outside air damper / economizer on hvac unit | $1,071 | $1,467 |
$1,071
22,860
kWh
|
- | - | - | |
| 06 | 2.8114: Change rate schedules or other changes in utility service | $6,158 | $12,000 | - | - | - | $6,158 | |
| 07 | 2.2511: Insulate bare equipment | $7,466 | $1,085 |
$6,298
135,404
kWh
|
$1,168
-
kW-mo/yr
|
- | - | |
| 08 | 3.4111: Use closed cycle process to minimize waste water production | $82,766 | $960 | - | - |
$82,766
-
Tgal
|
- | |
| TOTAL RECOMMENDED | $100,832 | $17,872 |
$10,414
223,328
kWh
|
$1,494
-
kW-mo/yr
|
$82,766
-
Tgal
|
$6,158 | ||
| TOTAL IMPLEMENTED | $10,642 | $3,125 |
$9,148
196,365
kWh
|
$1,494
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs