| Assessment Year | 2014 |
|---|---|
| Principal Product | Small electric motors |
| NAICS | 335312: Motor and Generator Manufacturing |
| SIC | 3621: Motors and Generators |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
200,000
ft2
|
| Annual Production | 2,200,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,464,928 | 21,888,160 |
kWh
|
$0.067 |
| Electricity Demand | $163,160 | 39,127 |
kW-mo/yr
|
$4.17 |
| Natural Gas | $85,115 | 8,166 |
MMBtu
|
$10.42 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $265,161 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $29,917 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $2,347 | $972 |
$2,347
35,030
kWh
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,605 | $30,150 |
$22,605
337,392
kWh
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,715 | $63,236 |
$26,715
398,736
kWh
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,202 | $16,590 |
$3,202
47,795
kWh
|
|
| 05 | 2.3512: De-energize excess transformer capacity | $3,687 | $8,925 |
$3,687
55,036
kWh
|
|
| 06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $206,605 | $247,740 |
$206,605
3,103,533
kWh
|
|
| TOTAL RECOMMENDED | $265,161 | $367,613 |
$265,161
3,977,522
kWh
|
||
| TOTAL IMPLEMENTED | $29,917 | $79,826 |
$29,917
446,531
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs