| Assessment Year | 2026 |
|---|---|
| Principal Product | hand tools |
| NAICS | 332216: Saw Blade and Handtool Manufacturing |
| SIC | 3423: Hand and Edge Tools, Except Machine Tools and Handsaws |
| Sales Range | $50 M to 100M |
| # of Employees | 391 |
| Plant Area |
240,000
ft2
|
| Annual Production | 24,000,000
pieces
|
| Production Hrs. Annual | 5,400
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,064,240 | 15,048,085 |
kWh
|
$0.071 | |
| Electricity Demand | $486,346 | 27,582 |
kW-mo/yr
|
$17.63 | |
| Electricity Fees | $(-7,018.0) | - |
|
- | |
| Natural Gas | $387,589 | 59,814 |
MMBtu
|
$6.48 | |
| Waste Disposal Costs | |||||
| Water Usage | $142,341 | 16,037 |
Tgal
|
$8.88 | |
| TOTAL YEARLY COSTS | $2,073,498 | ||||
| RECOMMENDED SAVINGS* | $71,119 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $27,876 | $17,100 |
$20,800
292,955
kWh
|
$7,076
-
kW-mo/yr
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $21,881 | - |
$16,326
229,950
kWh
|
$5,554
-
kW-mo/yr
|
- | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $8,670 | $3,600 | - | - |
$8,670
-
MMBtu
|
|
| 04 | 2.2414: Use waste heat from hot flue gases to preheat | $4,638 | $68,500 | - | - |
$4,638
-
MMBtu
|
|
| 05 | 2.4221: Install compressor air intakes in coolest locations | $3,231 | $830 |
$2,411
33,964
kWh
|
$820
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,214 | $4,160 |
$2,350
33,097
kWh
|
$864
-
kW-mo/yr
|
- | |
| 07 | 2.7135: Install occupancy sensors | $1,609 | $404 |
$1,227
17,278
kWh
|
$383
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $71,119 | $94,594 |
$43,114
607,244
kWh
|
$14,697
-
kW-mo/yr
|
$13,308
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs