Assessment Year 2025
Principal Product Food, Medical, and Pet Packaging
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2759: Commercial Printing, Not Elsewhere Classified
Sales Range $50
M
to 100
M
# of Employees 77
Plant Area 108,000
ft2
Annual Production 1,000,000
lb
Production Hrs. Annual 5,760
hrs
Location (State) Wisconsin

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $279,341 3,786,254
kWh
Electricity Demand $85,027 9,717
kW-mo/yr
Electricity Fees $(-3,050.0) -
Natural Gas $38,722 8,160
MMBtu
Waste Disposal Costs
Water Usage $8,383 1,665
Tgal
Water Disposal $8,383 1,665
Tgal
TOTAL YEARLY COSTS $416,805
RECOMMENDED SAVINGS* $28,801 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
01 2.8112: Combine utility meters $5,951 - - - $5,951 -
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $5,563 - - - $5,563 -
03 2.4323: Use optimum size and capacity equipment $5,155 $9,394 $4,582
62,082
kWh
$573
-
kW-mo/yr
- -
04 2.4231: Reduce the pressure of compressed air to the minimum required $3,627 - $3,121
42,285
kWh
$507
-
kW-mo/yr
- -
05 2.7224: Reduce space conditioning during non-working hours $2,394 $2,950 $785
10,637
kWh
$138
-
kW-mo/yr
- $1,470
-
MMBtu
06 2.4221: Install compressor air intakes in coolest locations $2,117 $1,677 $1,821
24,673
kWh
$296
-
kW-mo/yr
- -
07 2.4227: Use compressor air filters $1,633 $5,051 $1,404
19,028
kWh
$228
-
kW-mo/yr
- -
08 2.7221: Lower temperature during the winter season and vice-versa $968 - $497
6,730
kWh
$81
-
kW-mo/yr
- $391
-
MMBtu
09 2.3132: Recharge batteries on during off-peak demand periods $849 $1,650 - - $849 -
10 2.4111: Utilize energy-efficient belts and other improved mechanisms $544 $180 $468
6,345
kWh
$76
-
kW-mo/yr
- -
TOTAL RECOMMENDED $28,801 $20,902 $12,677
171,780
kWh
$1,899
-
kW-mo/yr
$12,363 $1,861
-
MMBtu
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs