| Assessment Year | 2025 |
|---|---|
| Principal Product | Food & Medical Caps and Enclosures |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 260 |
| Plant Area |
450,000
ft2
|
| Annual Production | 28,821
ton
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $2,393,735 | 42,081,386 |
kWh
|
$0.057 | |
| Electricity Demand | $748,357 | 44,416 |
kW-mo/yr
|
$16.85 | |
| Electricity Fees | $132,571 | - |
|
- | |
| Natural Gas | $18,596 | 2,588 |
MMBtu
|
$7.19 | |
| Waste Disposal Costs | |||||
| Water Usage | $49,853 | 7,000 |
Tgal
|
$7.12 | |
| TOTAL YEARLY COSTS | $3,343,112 | ||||
| RECOMMENDED SAVINGS* | $32,863 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,211 | $20,406 |
$12,656
222,037
kWh
|
$9,555
-
kW-mo/yr
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,724 | - |
$4,787
83,978
kWh
|
$1,938
-
kW-mo/yr
|
- | |
| 03 | 2.4224: Upgrade controls on compressors | $2,386 | $3,535 |
$1,698
29,795
kWh
|
$687
-
kW-mo/yr
|
- | |
| 04 | 2.3132: Recharge batteries on during off-peak demand periods | $1,542 | - | - | - | $1,542 | |
| TOTAL RECOMMENDED | $32,863 | $23,941 |
$19,141
335,810
kWh
|
$12,180
-
kW-mo/yr
|
$1,542 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs