| Assessment Year | 2025 |
|---|---|
| Principal Product | Envelopes |
| NAICS | 322230: Stationery Product Manufacturing |
| SIC | 2677: Envelopes |
| Sales Range | $10 M to 50M |
| # of Employees | 75 |
| Plant Area |
114,723
ft2
|
| Annual Production | 683,422,000
pieces
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $140,717 | 1,819,283 |
kWh
|
$0.077 |
| Electricity Demand | $147,255 | 8,041 |
kW-mo/yr
|
$18.31 |
| Electricity Fees | $30,851 | - |
|
- |
| Natural Gas | $11,924 | 1,603 |
MMBtu
|
$7.44 |
| TOTAL YEARLY COSTS | $330,747 | |||
| RECOMMENDED SAVINGS* | $30,028 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $25,950 | - | - |
$25,950
-
kW-mo/yr
|
- | |
| 02 | 2.7444: Close holes and openings in building such as broken windows | $1,959 | $6,000 | - | - |
$1,959
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,471 | $2,249 |
$782
10,159
kWh
|
$689
-
kW-mo/yr
|
- | |
| 04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $552 | $635 | - | - |
$552
-
MMBtu
|
|
| 05 | 2.7135: Install occupancy sensors | $96 | $368 |
$54
699
kWh
|
$42
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $30,028 | $9,252 |
$836
10,858
kWh
|
$26,681
-
kW-mo/yr
|
$2,511
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs