Assessment Year | 2024 |
---|---|
Principal Product | Electronic Control Manufacturer |
NAICS | 334417: Electronic Connector Manufacturing |
SIC | 3678: Electronic Connectors |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
25,000
ft2
|
Annual Production | 3,500
pieces
|
Production Hrs. Annual | 2,400
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $63,844 | 598,721 |
kWh
|
$0.11 | |
Electricity Demand | $24,086 | 3,178 |
kW-mo/yr
|
$7.58 | |
Electricity Fees | $19,685 | - |
|
- | |
Natural Gas | $12,370 | 1,750 |
MMBtu
|
$7.07 | |
Waste Disposal Costs | |||||
Water Usage | $8,740 | 2,102 |
Tgal
|
$4.16 | |
TOTAL YEARLY COSTS | $128,725 | ||||
RECOMMENDED SAVINGS* | $6,030 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,315 | $5,877 |
$3,373
31,528
kWh
|
$942
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,148 | - |
$848
7,923
kWh
|
$300
-
kW-mo/yr
|
- | |
03 | 2.7444: Close holes and openings in building such as broken windows | $464 | $603 | - | - |
$464
-
MMBtu
|
|
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $102 | $103 |
$76
706
kWh
|
$27
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $6,030 | $6,583 |
$4,297
40,157
kWh
|
$1,269
-
kW-mo/yr
|
$464
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs