| Assessment Year | 2024 |
|---|---|
| Principal Product | machined compenents |
| NAICS | 334413: Semiconductor and Related Device Manufacturing |
| SIC | 3674: Semiconductors and Related Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 220 |
| Plant Area |
42,500
ft2
|
| Annual Production | 15,000,000
pieces
|
| Production Hrs. Annual | 6,032
hrs
|
| Location (State) | Minnesota |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $212,263 | 2,812,084 |
kWh
|
$0.075 | |
| Electricity Demand | $91,683 | 7,574 |
kW-mo/yr
|
$12.10 | |
| Electricity Fees | $107,395 | - |
|
- | |
| Natural Gas | $26,118 | 2,236 |
MMBtu
|
$11.68 | |
| Waste Disposal Costs | |||||
| Water Usage | $37,295 | 2 |
Tgal
|
$16,952.27 | |
| TOTAL YEARLY COSTS | $474,754 | ||||
| RECOMMENDED SAVINGS* | $22,022 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,099 | $21,586 |
$10,299
137,320
kWh
|
$2,800
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,848 | $12,763 |
$4,689
62,514
kWh
|
$1,160
-
kW-mo/yr
|
- | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $2,034 | $4,262 |
$1,666
22,216
kWh
|
$368
-
kW-mo/yr
|
- | |
| 04 | 2.7224: Reduce space conditioning during non-working hours | $1,041 | - |
$275
3,663
kWh
|
$67
-
kW-mo/yr
|
$700
-
MMBtu
|
|
| TOTAL RECOMMENDED | $22,022 | $38,611 |
$16,928
225,713
kWh
|
$4,394
-
kW-mo/yr
|
$700
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs