| Assessment Year | 2022 |
|---|---|
| Principal Product | Paperboard Packaging |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2759: Commercial Printing, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 139 |
| Plant Area |
275,000
ft2
|
| Annual Production | 225,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $384,174 | 6,389,618 |
kWh
|
$0.060 | |
| Electricity Demand | $266,176 | 17,530 |
kW-mo/yr
|
$15.18 | |
| Electricity Fees | $60,560 | - |
|
- | |
| Natural Gas | $24,485 | 5,441 |
MMBtu
|
$4.50 | |
| Waste Disposal Costs | |||||
| Water Usage | $8,582 | 1,520 |
Tgal
|
$5.65 | |
| Water Disposal | $3,053 | 571 |
Tgal
|
$5.35 | |
| TOTAL YEARLY COSTS | $747,030 | ||||
| RECOMMENDED SAVINGS* | $69,835 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $26,531 | - |
$15,969
266,148
kWh
|
$5,360
-
kW-mo/yr
|
$5,202
-
MMBtu
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,525 | $2,725 |
$11,658
194,274
kWh
|
$5,867
-
kW-mo/yr
|
- | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $13,809 | - |
$7,477
124,615
kWh
|
- |
$6,332
-
MMBtu
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,314 | $3,500 |
$3,929
65,483
kWh
|
$1,385
-
kW-mo/yr
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,512 | $5,221 |
$2,224
37,066
kWh
|
$289
-
kW-mo/yr
|
- | |
| 06 | 2.7243: Improve air circulation with destratification fans / other methods | $2,076 | $6,500 |
$(-363.0)
6,050
kWh
|
- |
$2,439
-
MMBtu
|
|
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,078 | - |
$861
14,343
kWh
|
$217
-
kW-mo/yr
|
- | |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $990 | $1,000 |
$659
10,975
kWh
|
$331
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $69,835 | $18,946 |
$42,414
718,954
kWh
|
$13,448
-
kW-mo/yr
|
$13,973
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs