Assessment Year | 2021 |
---|---|
Principal Product | concrete plants |
NAICS | 333120: Construction Machinery Manufacturing |
SIC | 3531: Construction Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 83 |
Plant Area |
90,000
ft2
|
Annual Production | 32
pieces
|
Production Hrs. Annual | 4,048
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $80,670 | 1,357,001 |
kWh
|
$0.059 | |
Electricity Demand | $67,844 | 4,543 |
kW-mo/yr
|
$14.93 | |
Electricity Fees | $20,766 | - |
|
- | |
Natural Gas | $27,241 | 4,827 |
MMBtu
|
$5.64 | |
Waste Disposal Costs | |||||
Water Usage | $3,863 | 266 |
Tgal
|
$14.55 | |
TOTAL YEARLY COSTS | $200,384 | ||||
RECOMMENDED SAVINGS* | $26,657 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $1,198 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $12,220 | $10,675 | - | - |
$12,220
-
MMBtu
|
|
02 | 2.4322: Use or replace with energy efficient substitutes | $9,928 | $36,500 |
$6,368
107,116
kWh
|
$3,560
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,884 | $3,500 |
$1,209
20,331
kWh
|
$675
-
kW-mo/yr
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,198 | $2,170 |
$768
12,921
kWh
|
$430
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $1,099 | $1,200 |
$705
11,860
kWh
|
$394
-
kW-mo/yr
|
- | |
06 | 2.4239: Eliminate or reduce compressed air usage | $328 | $1,500 |
$328
5,521
kWh
|
- | - | |
TOTAL RECOMMENDED | $26,657 | $55,545 |
$9,378
157,749
kWh
|
$5,059
-
kW-mo/yr
|
$12,220
-
MMBtu
|
||
TOTAL IMPLEMENTED | $1,198 | $2,170 |
$768
12,921
kWh
|
$430
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs