Assessment Year | 2008 |
---|---|
Principal Product | Automotive Weather Stripping |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 720 |
Plant Area |
380,000
ft2
|
Annual Production | 9,000,000
ton
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $720,689 | 22,166,500 |
kWh
|
$0.033 |
Electricity Demand | $486,773 | 42,369 |
kW-mo/yr
|
$11.49 |
Electricity Fees | $37,177 | - |
|
- |
Natural Gas | $715,925 | 71,444 |
MMBtu
|
$10.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,602 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,425 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,410 | $50,325 |
$6,740
182,160
kWh
|
$4,000
-
kW-mo/yr
|
- | - | $2,670 | |
02 | 2.2443: Re-use or recycle hot or cold process exhaust air | $13,265 | $26,530 | - | - | - |
$13,265
-
MMBtu
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,100 | $2,500 |
$12,100
458,641
kWh
|
- | - | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $5,700 | $11,500 |
$5,700
143,119
kWh
|
- | - | - | - | |
05 | 2.4322: Use or replace with energy efficient substitutes | $3,200 | $11,200 | - | - | - | - | $3,200 | |
06 | 2.4224: Upgrade controls on compressors | $2,625 | $5,250 |
$1,815
49,056
kWh
|
$810
-
kW-mo/yr
|
- | - | - | |
07 | 2.3212: Optimize plant power factor | $8,302 | $48,000 | - | - | $8,302 | - | - | |
TOTAL RECOMMENDED | $58,602 | $155,305 |
$26,355
832,976
kWh
|
$4,810
-
kW-mo/yr
|
$8,302 |
$13,265
-
MMBtu
|
$5,870 | ||
TOTAL IMPLEMENTED | $20,425 | $19,250 |
$19,615
650,816
kWh
|
$810
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs