| Assessment Year | 2020 |
|---|---|
| Principal Product | Fuel Ethanol |
| NAICS | 311211: Flour Milling |
| SIC | 2041: Flour and Other Grain Mill Products |
| Sales Range | $100 M to 500M |
| # of Employees | 47 |
| Plant Area |
44,000
ft2
|
| Annual Production | 63,000
Tgal
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,976,966 | 51,058,800 |
kWh
|
$0.039 |
| Electricity Demand | $1,736,183 | 68,480 |
kW-mo/yr
|
$25.35 |
| Electricity Fees | $(-137,269.0) | - |
|
- |
| Natural Gas | $4,972,609 | 1,564,095 |
MMBtu
|
$3.18 |
| TOTAL YEARLY COSTS | $8,548,489 | |||
| RECOMMENDED SAVINGS* | $154,433 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $50,945 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1113: Reduce combustion air flow to optimum | $54,997 | $46,180 | - | - |
$54,997
-
MMBtu
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $50,357 | $43,670 |
$29,708
761,742
kWh
|
$20,649
-
kW-mo/yr
|
- | |
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $30,640 | $45,000 | - | - |
$30,640
-
MMBtu
|
|
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,843 | $3,560 |
$4,832
123,897
kWh
|
$3,011
-
kW-mo/yr
|
- | |
| 05 | 2.7135: Install occupancy sensors | $4,345 | $4,350 |
$2,676
68,606
kWh
|
$1,670
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,043 | $11,523 |
$2,489
63,845
kWh
|
$1,554
-
kW-mo/yr
|
- | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $841 | - |
$445
11,405
kWh
|
$396
-
kW-mo/yr
|
- | |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $780 | $1,585 |
$412
10,573
kWh
|
$367
-
kW-mo/yr
|
- | |
| 09 | 2.4224: Upgrade controls on compressors | $589 | $1,748 |
$311
7,983
kWh
|
$278
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $154,433 | $157,616 |
$40,873
1,048,051
kWh
|
$27,924
-
kW-mo/yr
|
$85,637
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $50,945 | $45,418 |
$30,019
769,725
kWh
|
$20,926
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs