Assessment Year | 2019 |
---|---|
Principal Product | OEM plastics Converting |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $50 M to 100M |
# of Employees | 170 |
Plant Area |
93,500
ft2
|
Annual Production | 10,000
units
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $103,975 | 1,474,800 |
kWh
|
$0.071 | |
Electricity Demand | $55,261 | 4,352 |
kW-mo/yr
|
$12.70 | |
Electricity Fees | $7,631 | - |
|
- | |
Natural Gas | $18,130 | 2,965 |
MMBtu
|
$6.11 | |
Waste Disposal Costs | |||||
Water Usage | $21,650 | 7,233 |
Tgal
|
$2.99 | |
TOTAL YEARLY COSTS | $206,647 | ||||
RECOMMENDED SAVINGS* | $20,958 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,749 | $27,082 |
$7,915
111,479
kWh
|
$1,834
-
kW-mo/yr
|
- | |
02 | 2.7132: Install timers on light switches in little used areas | $3,677 | $3,000 |
$3,400
47,881
kWh
|
$278
-
kW-mo/yr
|
- | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,191 | $3,200 |
$3,191
44,942
kWh
|
- | - | |
04 | 2.7444: Close holes and openings in building such as broken windows | $1,791 | $700 | - | - |
$1,791
-
MMBtu
|
|
05 | 2.7444: Close holes and openings in building such as broken windows | $1,170 | $570 | - | - |
$1,170
-
MMBtu
|
|
06 | 2.2437: Recover waste heat from equipment | $980 | $1,950 | - | - |
$980
-
MMBtu
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $400 | $675 |
$400
5,616
kWh
|
- | - | |
TOTAL RECOMMENDED | $20,958 | $37,177 |
$14,906
209,918
kWh
|
$2,112
-
kW-mo/yr
|
$3,941
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs