Assessment Year | 2018 |
---|---|
Principal Product | Glass |
NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231: Glass Products, Made of Purchased Glass |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
400,000
ft2
|
Annual Production | 3,250,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $864,008 | 17,481,169 |
kWh
|
$0.049 | |
Electricity Demand | $557,508 | 40,694 |
kW-mo/yr
|
$13.70 | |
Electricity Fees | $92,148 | - |
|
- | |
Natural Gas | $52,511 | 9,268 |
MMBtu
|
$5.67 | |
Waste Disposal Costs | |||||
Water Usage | $29,259 | 10,297 |
Tgal
|
$2.84 | |
TOTAL YEARLY COSTS | $1,595,434 | ||||
RECOMMENDED SAVINGS* | $107,851 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $11,376 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $67,159 | $96,417 |
$43,800
886,635
kWh
|
$23,359
-
kW-mo/yr
|
- | - | |
02 | 2.9114: Use solar heat to make electricty | $14,063 | $48,500 |
$14,063
272,353
kWh
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $11,035 | $26,000 |
$11,035
223,248
kWh
|
- | - | - | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $9,452 | $18,525 | - | - |
$9,452
-
MMBtu
|
- | |
05 | 2.7231: Use radiant heater for spot heating | $3,585 | $2,850 | - | - |
$3,585
-
MMBtu
|
- | |
06 | 2.3132: Recharge batteries on during off-peak demand periods | $1,558 | - | - | - | - | $1,558 | |
07 | 2.7134: Use photocell controls | $633 | $878 |
$633
12,807
kWh
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $366 | $1,616 |
$187
3,784
kWh
|
$71
-
kW-mo/yr
|
- | $108 | |
TOTAL RECOMMENDED | $107,851 | $194,786 |
$69,718
1,398,827
kWh
|
$23,430
-
kW-mo/yr
|
$13,037
-
MMBtu
|
$1,666 | ||
TOTAL IMPLEMENTED | $11,376 | $20,141 |
$187
3,784
kWh
|
$71
-
kW-mo/yr
|
$9,452
-
MMBtu
|
$1,666 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs