Assessment Year | 2018 |
---|---|
Principal Product | Brake systems and components for recreational vehicles |
NAICS | 336340: Motor Vehicle Brake System Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 230 |
Plant Area |
160,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $263,491 | 4,019,160 |
kWh
|
$0.066 | |
Electricity Demand | $127,584 | 9,246 |
kW-mo/yr
|
$13.80 | |
Electricity Fees | $336 | - |
|
- | |
Natural Gas | $17,738 | 2,689 |
MMBtu
|
$6.60 | |
Waste Disposal Costs | |||||
Water Usage | $800 | 1 |
Tgal
|
$800.00 | |
TOTAL YEARLY COSTS | $409,949 | ||||
RECOMMENDED SAVINGS* | $87,783 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $6,538 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $36,186 | $37,500 |
$36,186
551,615
kWh
|
- | - | - | |
02 | 2.9114: Use solar heat to make electricty | $18,171 | $48,514 |
$18,171
277,168
kWh
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,300 | $9,602 |
$9,941
151,632
kWh
|
$4,359
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,136 | $2,000 |
$2,880
43,893
kWh
|
$1,256
-
kW-mo/yr
|
- | - | |
05 | 2.7221: Lower temperature during the winter season and vice-versa | $3,828 | - |
$3,828
58,354
kWh
|
- | - | - | |
06 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $2,944 | $3,500 |
$2,944
44,908
kWh
|
- | - | - | |
07 | 2.7231: Use radiant heater for spot heating | $2,840 | $2,472 | - | - | - |
$2,840
-
MMBtu
|
|
08 | 2.2511: Insulate bare equipment | $2,412 | $666 |
$2,412
36,796
kWh
|
- | - | - | |
09 | 2.3132: Recharge batteries on during off-peak demand periods | $2,110 | - | - | - | $2,110 | - | |
10 | 2.7447: Install vinyl strip / high speed / air curtain doors | $600 | $1,511 | - | - | - |
$600
-
MMBtu
|
|
11 | 2.7134: Use photocell controls | $256 | $47 |
$256
3,905
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $87,783 | $105,812 |
$76,618
1,168,271
kWh
|
$5,615
-
kW-mo/yr
|
$2,110 |
$3,440
-
MMBtu
|
||
TOTAL IMPLEMENTED | $6,538 | $1,511 |
$3,828
58,354
kWh
|
- | $2,110 |
$600
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs