Assessment Year | 2018 |
---|---|
Principal Product | Hydraulic valves |
NAICS | 332912: Fluid Power Valve and Hose Fitting Manufacturing |
SIC | 3492: Fluid Power Valves and Hose Fittings |
Sales Range | $100 M to 500M |
# of Employees | 213 |
Plant Area |
70,000
ft2
|
Annual Production | 10,749,234
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,384,683 | 20,767,190 |
kWh
|
$0.067 |
Electricity Demand | $664,477 | 49,758 |
kW-mo/yr
|
$13.35 |
Electricity Fees | $55,579 | - |
|
- |
Natural Gas | $91,867 | 23,805 |
MMBtu
|
$3.86 |
TOTAL YEARLY COSTS | $2,196,606 | |||
RECOMMENDED SAVINGS* | $112,190 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,172 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $39,371 | $117,000 |
$39,371
590,443
kWh
|
- | - | |
02 | 2.9114: Use solar heat to make electricty | $18,489 | $72,000 |
$18,489
277,273
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,355 | $11,813 |
$10,407
156,073
kWh
|
$3,948
-
kW-mo/yr
|
- | |
04 | 2.7226: Use computer programs to optimize hvac performance | $11,817 | - | - | - |
$11,817
-
MMBtu
|
|
05 | 2.7231: Use radiant heater for spot heating | $8,183 | $8,250 | - | - |
$8,183
-
MMBtu
|
|
06 | 2.2135: Repair and eliminate steam leaks | $6,333 | $2,250 |
$4,970
74,534
kWh
|
$1,363
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $4,115 | $3,020 |
$2,571
38,554
kWh
|
$1,544
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,953 | $5,010 |
$3,953
74,854
kWh
|
- | - | |
09 | 2.7134: Use photocell controls | $2,253 | $840 |
$834
12,511
kWh
|
$1,419
-
kW-mo/yr
|
- | |
10 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,400 | $2,776 | - | - |
$1,400
-
MMBtu
|
|
11 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,207 | $1,980 | - | - |
$1,207
-
MMBtu
|
|
12 | 2.7135: Install occupancy sensors | $262 | $262 |
$205
3,079
kWh
|
$57
-
kW-mo/yr
|
- | |
13 | 2.2511: Insulate bare equipment | $255 | $510 |
$117
1,756
kWh
|
$138
-
kW-mo/yr
|
- | |
14 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $197 | $527 |
$154
2,313
kWh
|
$43
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $112,190 | $226,238 |
$81,071
1,231,390
kWh
|
$8,512
-
kW-mo/yr
|
$22,607
-
MMBtu
|
||
TOTAL IMPLEMENTED | $26,172 | $11,813 |
$10,407
156,073
kWh
|
$3,948
-
kW-mo/yr
|
$11,817
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs