Assessment Year 2017
Principal Product HVAC Eqiupment
NAICS 332322: Sheet Metal Work Manufacturing
SIC 3564: Industrial and Commercial Fans and Blowers and Air Purification Equipment
Sales Range $50
M
to 100
M
# of Employees 100
Plant Area 220,000
ft2
Annual Production 1,137,498
units
Production Hrs. Annual 2,000
hrs
Location (State) Wisconsin

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $90,459 1,750,367
kWh
Electricity Demand $59,390 4,335
kW-mo/yr
Electricity Fees $4,893 -
Natural Gas $48,734 9,665
MMBtu
Waste Disposal Costs
Water Usage $14,200 3,352
Tgal
Water Disposal $10,040 3,352
Tgal
TOTAL YEARLY COSTS $227,716
RECOMMENDED SAVINGS* $42,456 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $13,294

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
01 2.9114: Use solar heat to make electricty $14,609 $72,000 $14,609
282,681
kWh
- - - -
02 2.7134: Use photocell controls $3,191 $10,230 $3,191
61,752
kWh
- - - -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $7,895 $14,722 $3,048
58,972
kWh
$4,847
-
kW-mo/yr
- - -
04 2.2414: Use waste heat from hot flue gases to preheat $7,112 $14,000 - - $7,112
-
MMBtu
- -
05 3.4153: Use counter current rinsing to reduce waste water $3,017 $3,000 - - - $3,017
-
Tgal
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,729 $1,833 $908
17,564
kWh
$659
-
kW-mo/yr
- - $162
07 2.2113: Repair or replace steam traps $1,678 $3,960 - - $1,678
-
MMBtu
- -
08 2.1221: Replace obsolete burners with more efficient ones $1,597 $3,400 - - $1,597
-
MMBtu
- -
09 2.4221: Install compressor air intakes in coolest locations $1,233 $3,124 $475
9,212
kWh
$758
-
kW-mo/yr
- - -
10 2.7142: Utilize higher efficiency lamps and/or ballasts $395 $720 $195
3,767
kWh
$71
-
kW-mo/yr
- - $129
TOTAL RECOMMENDED $42,456 $126,989 $22,426
433,948
kWh
$6,335
-
kW-mo/yr
$10,387
-
MMBtu
$3,017
-
Tgal
$291
TOTAL IMPLEMENTED $13,294 $24,635 $4,150
80,303
kWh
$5,577
-
kW-mo/yr
$3,275
-
MMBtu
- $291
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs