Assessment Year | 2017 |
---|---|
Principal Product | Commercial Printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
400,000
ft2
|
Annual Production | 1,000,000,000
units
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $607,990 | 9,782,009 |
kWh
|
$0.062 |
Electricity Demand | $195,959 | 24,347 |
kW-mo/yr
|
$8.05 |
Natural Gas | $110,383 | 51,698 |
MMBtu
|
$2.14 |
TOTAL YEARLY COSTS | $914,332 | |||
RECOMMENDED SAVINGS* | $41,228 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $251 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $25,590 | $22,000 |
$21,782
337,398
kWh
|
$3,808
-
kW-mo/yr
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,976 | $25,932 |
$6,976
108,224
kWh
|
- | |
03 | 2.6231: Utilize controls to operate equipment only when needed | $2,523 | $260 |
$2,523
39,080
kWh
|
- | |
04 | 2.7135: Install occupancy sensors | $2,778 | $1,590 |
$2,160
33,455
kWh
|
$618
-
kW-mo/yr
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,320 | $6,300 |
$1,975
30,590
kWh
|
$345
-
kW-mo/yr
|
|
06 | 2.7134: Use photocell controls | $545 | $885 |
$279
4,319
kWh
|
$266
-
kW-mo/yr
|
|
07 | 2.6127: Maintain air filters by cleaning or replacement | $251 | $200 |
$251
3,888
kWh
|
- | |
08 | 2.7424: Shade windows from summer sun | $245 | $210 |
$209
3,238
kWh
|
$36
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $41,228 | $57,377 |
$36,155
560,192
kWh
|
$5,074
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $251 | $200 |
$251
3,888
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs