ITAC Assessment: WM0096
ITAC logo
ITAC Assessment: WM0096
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2016
Principal Product Toner Cartridges & Small Electronic Devices
NAICS 333316: Photographic and Photocopying Equipment Manufacturing
SIC 3577: Computer Peripheral Equipment, Not Elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 190
Plant Area 315,664
ft2
Annual Production 4,800,000
units
Production Hrs. Annual 2,080
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $117,613 2,099,114
kWh
Electricity Demand $24,518 6,010
kW-mo/yr
Electricity Fees $33,540 -
Natural Gas $52,253 8,965
MMBtu
Waste Disposal Costs
Water Usage $4,839 654
Tgal
Solid Waste (non-haz) $7,326 25,280
lb
TOTAL YEARLY COSTS $240,089
RECOMMENDED SAVINGS* $31,648 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $25,675

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $22,885 $59,248 $17,447
311,551
kWh
$5,438
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $2,510 $5,375 $2,510
44,824
kWh
- -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,504 $1,270 $1,763
31,486
kWh
$741
-
kW-mo/yr
-
04 2.4231: Reduce the pressure of compressed air to the minimum required $910 - $640
11,433
kWh
$269
-
kW-mo/yr
-
05 2.4221: Install compressor air intakes in coolest locations $606 $2,250 $426
7,613
kWh
$179
-
kW-mo/yr
-
06 2.7231: Use radiant heater for spot heating $869 $1,230 - - $869
-
MMBtu
07 2.7134: Use photocell controls $428 $396 $313
5,590
kWh
$115
-
kW-mo/yr
-
08 2.7135: Install occupancy sensors $418 $1,015 $319
5,694
kWh
$99
-
kW-mo/yr
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $280 $242 $253
4,512
kWh
$27
-
kW-mo/yr
-
10 2.7135: Install occupancy sensors $238 $576 $217
3,870
kWh
$22
-
kW-mo/yr
-
TOTAL RECOMMENDED $31,648 $71,602 $23,888
426,573
kWh
$6,891
-
kW-mo/yr
$869
-
MMBtu
TOTAL IMPLEMENTED $25,675 $64,865 $20,210
360,887
kWh
$5,465
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs