Assessment Year | 2016 |
---|---|
Principal Product | Toner Cartridges & Small Electronic Devices |
NAICS | 333316: Photographic and Photocopying Equipment Manufacturing |
SIC | 3577: Computer Peripheral Equipment, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 190 |
Plant Area |
315,664
ft2
|
Annual Production | 4,800,000
units
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $117,613 | 2,099,114 |
kWh
|
$0.056 | |
Electricity Demand | $24,518 | 6,010 |
kW-mo/yr
|
$4.08 | |
Electricity Fees | $33,540 | - |
|
- | |
Natural Gas | $52,253 | 8,965 |
MMBtu
|
$5.83 | |
Waste Disposal Costs | |||||
Water Usage | $4,839 | 654 |
Tgal
|
$7.40 | |
Solid Waste (non-haz) | $7,326 | 25,280 |
lb
|
$0.29 | |
TOTAL YEARLY COSTS | $240,089 | ||||
RECOMMENDED SAVINGS* | $31,648 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $25,675 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,885 | $59,248 |
$17,447
311,551
kWh
|
$5,438
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,510 | $5,375 |
$2,510
44,824
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,504 | $1,270 |
$1,763
31,486
kWh
|
$741
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $910 | - |
$640
11,433
kWh
|
$269
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $606 | $2,250 |
$426
7,613
kWh
|
$179
-
kW-mo/yr
|
- | |
06 | 2.7231: Use radiant heater for spot heating | $869 | $1,230 | - | - |
$869
-
MMBtu
|
|
07 | 2.7134: Use photocell controls | $428 | $396 |
$313
5,590
kWh
|
$115
-
kW-mo/yr
|
- | |
08 | 2.7135: Install occupancy sensors | $418 | $1,015 |
$319
5,694
kWh
|
$99
-
kW-mo/yr
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $280 | $242 |
$253
4,512
kWh
|
$27
-
kW-mo/yr
|
- | |
10 | 2.7135: Install occupancy sensors | $238 | $576 |
$217
3,870
kWh
|
$22
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $31,648 | $71,602 |
$23,888
426,573
kWh
|
$6,891
-
kW-mo/yr
|
$869
-
MMBtu
|
||
TOTAL IMPLEMENTED | $25,675 | $64,865 |
$20,210
360,887
kWh
|
$5,465
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |