Assessment Year | 2016 |
---|---|
Principal Product | Single use plastic food lids, containers |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
87,500
ft2
|
Annual Production | 6,000,000
units
|
Production Hrs. Annual | 5,800
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $334,105 | 8,121,919 |
kWh
|
$0.041 | |
Electricity Demand | $337,478 | 19,776 |
kW-mo/yr
|
$17.07 | |
Electricity Fees | $251,816 | - |
|
- | |
Natural Gas | $11,749 | 1,651 |
MMBtu
|
$7.12 | |
Waste Disposal Costs | |||||
Water Usage | $22,174 | 2,368,168 |
Tgal
|
$0.009 | |
TOTAL YEARLY COSTS | $957,322 | ||||
RECOMMENDED SAVINGS* | $173,709 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $3,245 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $71,275 | $132,797 | - |
$35,938
-
kW-mo/yr
|
$35,337 | - | - | |
02 | 2.2437: Recover waste heat from equipment | $75,376 | $50,000 |
$40,615
984,608
kWh
|
$34,761
-
kW-mo/yr
|
- | - | - | |
03 | 2.2437: Recover waste heat from equipment | $9,940 | $28,000 | - | - | - |
$9,940
-
MMBtu
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $8,075 | $501 |
$4,815
116,800
kWh
|
$3,260
-
kW-mo/yr
|
- | - | - | |
05 | 3.4155: Meter waste water | $4,267 | $375 | - | - | - | - | $4,267 | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $3,245 | - | - | - | - |
$3,245
-
MMBtu
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,531 | $6,000 |
$848
20,545
kWh
|
$683
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $173,709 | $217,673 |
$46,278
1,121,953
kWh
|
$74,642
-
kW-mo/yr
|
$35,337 |
$13,185
-
MMBtu
|
$4,267 | ||
TOTAL IMPLEMENTED | $3,245 | - | - | - | - |
$3,245
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs