Assessment Year | 2016 |
---|---|
Principal Product | Butyl Flashing Tape |
NAICS | 325520: Adhesive Manufacturing |
SIC | 2891: Adhesives and Sealants |
Sales Range | $10 M to 50M |
# of Employees | 254 |
Plant Area |
223,889
ft2
|
Annual Production | 1,800
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $298,289 | 4,477,600 |
kWh
|
$0.067 |
Electricity Demand | $148,787 | 10,866 |
kW-mo/yr
|
$13.69 |
Natural Gas | $140,661 | 24,897 |
MMBtu
|
$5.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $89,717 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,828 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,124 | $83,912 |
$11,602
174,156
kWh
|
$8,522
-
kW-mo/yr
|
- | |
02 | 2.2437: Recover waste heat from equipment | $17,305 | $34,684 | - | - |
$17,305
-
MMBtu
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,763 | $15,500 |
$15,763
235,851
kWh
|
- | - | |
04 | 2.4226: Use / purchase optimum sized compressor | $11,145 | - |
$11,145
167,295
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,605 | $1,900 |
$5,905
88,642
kWh
|
$1,700
-
kW-mo/yr
|
- | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $4,665 | - | - | - |
$4,665
-
MMBtu
|
|
07 | 2.7135: Install occupancy sensors | $4,032 | $9,450 |
$4,032
61,102
kWh
|
- | - | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,103 | $400 |
$3,103
46,578
kWh
|
- | - | |
09 | 2.2511: Insulate bare equipment | $1,819 | $409 | - | - |
$1,819
-
MMBtu
|
|
10 | 2.4314: Use synthetic lubricant | $1,724 | $630 |
$1,724
25,877
kWh
|
- | - | |
11 | 2.4239: Eliminate or reduce compressed air usage | $1,465 | - |
$1,465
21,995
kWh
|
- | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $866 | $1,988 |
$866
12,999
kWh
|
- | - | |
13 | 2.6211: Conserve energy by efficient use of vending machines | $101 | $402 |
$87
1,304
kWh
|
$14
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $89,717 | $149,275 |
$55,692
835,799
kWh
|
$10,235
-
kW-mo/yr
|
$23,789
-
MMBtu
|
||
TOTAL IMPLEMENTED | $37,828 | $88,200 |
$22,942
344,370
kWh
|
$10,221
-
kW-mo/yr
|
$4,665
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs