Assessment Year | 2015 |
---|---|
Principal Product | NA |
NAICS | 221310: Water Supply and Irrigation Systems |
SIC | 4941: Water Supply |
Sales Range | $1 M to 5M |
# of Employees | 8 |
Plant Area |
65,000
ft2
|
Annual Production | 14,000,000
Tgal
|
Production Hrs. Annual | 8,600
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $817,888 | 13,488,823 |
kWh
|
$0.061 |
Electricity Demand | $271,883 | 21,960 |
kW-mo/yr
|
$12.38 |
Electricity Fees | $28,387 | - |
|
- |
Natural Gas | $87,828 | 16,587 |
MMBtu
|
$5.29 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $68,361 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4131: Size electric motors for peak operating efficiency | $37,683 | $5,100 | - |
$37,683
-
kW-mo/yr
|
- | |
02 | 2.4314: Use synthetic lubricant | $16,750 | $9,000 |
$13,081
215,745
kWh
|
$3,669
-
kW-mo/yr
|
- | |
03 | 2.4224: Upgrade controls on compressors | $4,570 | $16,350 |
$4,570
75,370
kWh
|
- | - | |
04 | 2.7135: Install occupancy sensors | $3,296 | $1,875 |
$857
14,134
kWh
|
$2,439
-
kW-mo/yr
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,283 | $800 |
$1,814
29,910
kWh
|
$470
-
kW-mo/yr
|
- | |
06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $2,055 | $1,000 | - | - |
$2,055
-
MMBtu
|
|
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $867 | $3,330 |
$341
5,616
kWh
|
$526
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $627 | $2,391 |
$627
10,337
kWh
|
- | - | |
09 | 2.2511: Insulate bare equipment | $230 | $77 | - | - |
$230
-
MMBtu
|
|
TOTAL RECOMMENDED | $68,361 | $39,923 |
$21,289
351,112
kWh
|
$44,787
-
kW-mo/yr
|
$2,285
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs