| Assessment Year | 2014 |
|---|---|
| Principal Product | Architectural Doors |
| NAICS | 321911: Wood Window and Door Manufacturing |
| SIC | 2431: Millwork |
| Sales Range | $10 M to 50M |
| # of Employees | 173 |
| Plant Area |
700,000
ft2
|
| Annual Production | 130,000
units
|
| Production Hrs. Annual | 4,200
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $532,123 | 8,147,681 |
kWh
|
$0.065 |
| Electricity Demand | $187,856 | 23,482 |
kW-mo/yr
|
$8.00 |
| Electricity Fees | $(-16,649.0) | - |
|
- |
| Natural Gas | $748,932 | 112,139 |
MMBtu
|
$6.68 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $80,621 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,492 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $21,391 | $35,000 | - | - | - |
$21,391
-
MMBtu
|
|
| 02 | 2.2437: Recover waste heat from equipment | $10,441 | $4,500 | - | - | - |
$10,441
-
MMBtu
|
|
| 03 | 2.2511: Insulate bare equipment | $133 | $122 | - | - | - |
$133
-
MMBtu
|
|
| 04 | 2.3134: Shift from daytime to nighttime operation | $2,200 | - | - | - | $2,200 | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,235 | $2,200 |
$6,235
95,487
kWh
|
- | - | - | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $4,046 | $302 |
$3,233
49,504
kWh
|
$813
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,492 | $1,470 |
$2,972
47,515
kWh
|
$520
-
kW-mo/yr
|
- | - | |
| 08 | 2.7134: Use photocell controls | $2,825 | $1,125 |
$2,201
33,864
kWh
|
$624
-
kW-mo/yr
|
- | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,273 | $9,911 |
$11,113
170,976
kWh
|
$3,160
-
kW-mo/yr
|
- | - | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,633 | $10,068 |
$7,505
115,424
kWh
|
$2,128
-
kW-mo/yr
|
- | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,180 | $7,175 |
$3,580
54,829
kWh
|
$600
-
kW-mo/yr
|
- | - | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,772 | $7,640 |
$1,772
31,870
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $80,621 | $79,513 |
$38,611
599,469
kWh
|
$7,845
-
kW-mo/yr
|
$2,200 |
$31,965
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $3,492 | $1,470 |
$2,972
47,515
kWh
|
$520
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs