Assessment Year | 2012 |
---|---|
Principal Product | Industrial Absorbents |
NAICS | 322299: All Other Converted Paper Product Manufacturing |
SIC | 2679: Converted Paper and Paperboard Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 60 |
Plant Area |
135,000
ft2
|
Annual Production | 9,200,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $220,937 | 4,142,814 |
kWh
|
$0.053 |
Electricity Demand | $83,157 | 9,633 |
kW-mo/yr
|
$8.63 |
Natural Gas | $10,772 | 1,337 |
MMBtu
|
$8.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $8,584 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,617 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,254 | $600 |
$793
11,664
kWh
|
$461
-
kW-mo/yr
|
- | - | |
02 | 2.7135: Install occupancy sensors | $2,091 | - |
$2,091
39,945
kWh
|
- | - | - | |
03 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $2,223 | - |
$1,406
20,674
kWh
|
$817
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $226 | $120 |
$143
2,099
kWh
|
$83
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $137 | $360 |
$127
2,383
kWh
|
$10
-
kW-mo/yr
|
- | - | |
06 | 2.7444: Close holes and openings in building such as broken windows | $493 | $99 | - | - |
$493
-
MMBtu
|
- | |
07 | 3.1191: Change procedures / equipment / operating conditions | $2,160 | $900 | - | - | - | $2,160 | |
TOTAL RECOMMENDED | $8,584 | $2,079 |
$4,560
76,765
kWh
|
$1,371
-
kW-mo/yr
|
$493
-
MMBtu
|
$2,160 | ||
TOTAL IMPLEMENTED | $1,617 | $1,080 |
$1,063
16,146
kWh
|
$554
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs