Assessment Year | 2006 |
---|---|
Principal Product | Assembley and Testing of PCB |
NAICS | 334412: Bare Printed Circuit Board Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 140 |
Plant Area |
60,000
ft2
|
Annual Production | 3,600,000
units
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $95,506 | 2,862,000 |
kWh
|
$0.033 |
Electricity Demand | $65,825 | 6,174 |
kW-mo/yr
|
$10.66 |
Natural Gas | $23,367 | 2,502 |
MMBtu
|
$9.34 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $179,338 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,218 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.424: Improve space comfort conditioning | $156,640 | $48,500 | - | - | - | $156,640 | |
02 | 4.424: Improve space comfort conditioning | $9,074 | $900 | - | - | - | $9,074 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,466 | $6,300 |
$1,313
37,515
kWh
|
$1,153
-
kW-mo/yr
|
- | - | |
04 | 2.7124: Make a practice of turning off lights when not needed | $665 | - |
$352
10,063
kWh
|
$313
-
kW-mo/yr
|
- | - | |
05 | 2.2514: Cover open tanks | $2,414 | - |
$2,414
68,969
kWh
|
- | - | - | |
06 | 2.2437: Recover waste heat from equipment | $2,412 | - | - | - |
$2,412
-
MMBtu
|
- | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,678 | - |
$571
16,318
kWh
|
$1,107
-
kW-mo/yr
|
- | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $1,289 | $640 |
$573
16,362
kWh
|
$716
-
kW-mo/yr
|
- | - | |
09 | 2.3134: Shift from daytime to nighttime operation | $1,616 | - | - |
$1,616
-
kW-mo/yr
|
- | - | |
10 | 2.7442: Keep doors and windows shut when not on use | $1,084 | - | - | - |
$1,084
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $179,338 | $56,340 |
$5,223
149,227
kWh
|
$4,905
-
kW-mo/yr
|
$3,496
-
MMBtu
|
$165,714 | ||
TOTAL IMPLEMENTED | $13,218 | $7,200 |
$1,884
53,833
kWh
|
$2,260
-
kW-mo/yr
|
- | $9,074 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs