Assessment Year 2006
Principal Product Assembley and Testing of PCB
NAICS 334412: Bare Printed Circuit Board Manufacturing
SIC 3679: Electronic Components, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 140
Plant Area 60,000
ft2
Annual Production 3,600,000
units
Production Hrs. Annual 4,250
hrs
Location (State) Wisconsin

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $95,506 2,862,000
kWh
Electricity Demand $65,825 6,174
kW-mo/yr
Natural Gas $23,367 2,502
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $179,338 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $13,218

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
01 4.424: Improve space comfort conditioning $156,640 $48,500 - - - $156,640
02 4.424: Improve space comfort conditioning $9,074 $900 - - - $9,074
03 2.7142: Utilize higher efficiency lamps and/or ballasts $2,466 $6,300 $1,313
37,515
kWh
$1,153
-
kW-mo/yr
- -
04 2.7124: Make a practice of turning off lights when not needed $665 - $352
10,063
kWh
$313
-
kW-mo/yr
- -
05 2.2514: Cover open tanks $2,414 - $2,414
68,969
kWh
- - -
06 2.2437: Recover waste heat from equipment $2,412 - - - $2,412
-
MMBtu
-
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,678 - $571
16,318
kWh
$1,107
-
kW-mo/yr
- -
08 2.4221: Install compressor air intakes in coolest locations $1,289 $640 $573
16,362
kWh
$716
-
kW-mo/yr
- -
09 2.3134: Shift from daytime to nighttime operation $1,616 - - $1,616
-
kW-mo/yr
- -
10 2.7442: Keep doors and windows shut when not on use $1,084 - - - $1,084
-
MMBtu
-
TOTAL RECOMMENDED $179,338 $56,340 $5,223
149,227
kWh
$4,905
-
kW-mo/yr
$3,496
-
MMBtu
$165,714
TOTAL IMPLEMENTED $13,218 $7,200 $1,884
53,833
kWh
$2,260
-
kW-mo/yr
- $9,074
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs