Assessment Year | 2005 |
---|---|
Principal Product | Cardboard boxes |
NAICS | 322130: Paperboard Mills |
SIC | 2631: Paperboard Mills |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
189,000
ft2
|
Annual Production | 1,700,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $159,605 | 4,966,600 |
kWh
|
$0.032 |
Electricity Demand | $89,316 | 11,707 |
kW-mo/yr
|
$7.63 |
Natural Gas | $429,698 | 60,173 |
MMBtu
|
$7.14 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $188,567 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,118 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $162,672 | $360,000 |
$183,060
5,400,000
kWh
|
$86,940
-
kW-mo/yr
|
$(-107,328.0)
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,256 | $32,760 |
$9,668
285,180
kWh
|
$4,588
-
kW-mo/yr
|
- | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $3,320 | $360 | - | - |
$3,320
-
MMBtu
|
|
04 | 2.1123: Install automatic stack damper | $2,655 | $3,400 |
$2,655
78,330
kWh
|
- | - | |
05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,165 | - | - |
$2,165
-
kW-mo/yr
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,800 | $1,280 |
$1,180
34,813
kWh
|
$620
-
kW-mo/yr
|
- | |
07 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $1,135 | $1,500 | - | - |
$1,135
-
MMBtu
|
|
08 | 2.7124: Make a practice of turning off lights when not needed | $322 | $150 |
$322
9,511
kWh
|
- | - | |
09 | 2.3132: Recharge batteries on during off-peak demand periods | $242 | $200 | - |
$242
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $188,567 | $399,650 |
$196,885
5,807,834
kWh
|
$94,555
-
kW-mo/yr
|
$(-102,873.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $21,118 | $34,820 |
$9,668
285,180
kWh
|
$6,995
-
kW-mo/yr
|
$4,455
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs