Assessment Year | 2003 |
---|---|
Principal Product | 35000 |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 600 |
Plant Area |
295,000
ft2
|
Annual Production | 70,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,362,009 | 46,937,747 |
kWh
|
$0.029 |
Electricity Demand | $446,589 | 75,358 |
kW-mo/yr
|
$5.93 |
Electricity Fees | $325,646 | - |
|
- |
Natural Gas | $506,120 | 96,045 |
MMBtu
|
$5.27 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,734 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $21,502 | $30,000 |
$21,502
704,970
kWh
|
- | - | - | - | - | |
02 | 3.3132: Use reverse osmosis to concentrate material | $14,092 | $36,000 |
$(-2,500.0)
(-81,967)
kWh
|
- | - | - |
$17,242
-
Tgal
|
$(-650.0) | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,847 | $3,433 |
$8,229
269,803
kWh
|
$1,618
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,486 | $500 | - | - | - |
$3,486
-
MMBtu
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $7,048 | $1,280 |
$5,773
189,274
kWh
|
$1,275
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.3132: Recharge batteries on during off-peak demand periods | $2,005 | $1,400 | - |
$1,670
-
kW-mo/yr
|
$335 | - | - | - | |
07 | 2.2511: Insulate bare equipment | $754 | $294 | - | - | - |
$754
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $58,734 | $72,907 |
$33,004
1,082,080
kWh
|
$4,563
-
kW-mo/yr
|
$335 |
$4,240
-
MMBtu
|
$17,242
-
Tgal
|
$(-650.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs