Assessment Year | 2002 |
---|---|
Principal Product | stainless utensils |
NAICS |
n/a
|
SIC | 3421: Cutlery |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
610,000
ft2
|
Annual Production | 20,000,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $272,521 | 12,700,800 |
kWh
|
$0.021 |
Electricity Demand | $203,106 | 27,223 |
kW-mo/yr
|
$7.46 |
Electricity Fees | $135,852 | - |
|
- |
Natural Gas | $435,878 | 107,033 |
MMBtu
|
$4.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $156,166 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,915 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 3.3132: Use reverse osmosis to concentrate material | $133,384 | $140,000 |
$(-2,400.0)
(-50,000)
kWh
|
- |
$142,284
-
Tgal
|
$(-6,500.0) | |
02 | 2.7135: Install occupancy sensors | $9,841 | $25,000 |
$4,935
219,324
kWh
|
$4,906
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $5,168 | $11,700 |
$5,168
229,698
kWh
|
- | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,746 | $12,600 |
$3,746
166,507
kWh
|
- | - | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,556 | $740 |
$931
41,382
kWh
|
$625
-
kW-mo/yr
|
- | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,280 | $2,832 |
$806
35,808
kWh
|
$474
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,191 | $588 |
$702
31,200
kWh
|
$489
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $156,166 | $193,460 |
$13,888
673,919
kWh
|
$6,494
-
kW-mo/yr
|
$142,284
-
Tgal
|
$(-6,500.0) | ||
TOTAL IMPLEMENTED | $7,915 | $13,028 |
$6,801
302,280
kWh
|
$1,114
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs