Assessment Year | 2002 |
---|---|
Principal Product | Envelopes |
NAICS |
n/a
|
SIC | 2677: Envelopes |
Sales Range | $1 M to 5M |
# of Employees | 160 |
Plant Area |
300,000
ft2
|
Annual Production | 7,200,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $185,704 | 5,802,264 |
kWh
|
$0.032 |
Electricity Demand | $132,713 | 13,738 |
kW-mo/yr
|
$9.66 |
Electricity Fees | $24,565 | - |
|
- |
Natural Gas | $70,353 | 8,426 |
MMBtu
|
$8.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $54,886 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,805 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $15,331 | $2,200 | - | - |
$15,331
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,921 | $15,527 |
$6,505
203,280
kWh
|
$3,416
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $6,222 | $9,800 |
$3,187
99,582
kWh
|
$3,035
-
kW-mo/yr
|
- | - | |
04 | 2.7144: Install spectral reflectors / delamp | $5,203 | - |
$3,599
112,460
kWh
|
$1,604
-
kW-mo/yr
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,879 | $1,996 |
$4,655
145,470
kWh
|
$2,224
-
kW-mo/yr
|
- | - | |
06 | 2.7243: Improve air circulation with destratification fans / other methods | $4,308 | $8,000 |
$(-517.0)
(-15,400)
kWh
|
- |
$4,825
-
MMBtu
|
- | |
07 | 3.7137: Replace cloth rags with paper towels | $3,427 | - | - | - | - | $3,427 | |
08 | 2.4221: Install compressor air intakes in coolest locations | $1,941 | $740 |
$1,273
39,787
kWh
|
$668
-
kW-mo/yr
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,654 | $6,100 |
$1,654
49,236
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $54,886 | $44,363 |
$20,356
634,415
kWh
|
$10,947
-
kW-mo/yr
|
$20,156
-
MMBtu
|
$3,427 | ||
TOTAL IMPLEMENTED | $49,805 | $38,263 |
$18,702
585,179
kWh
|
$10,947
-
kW-mo/yr
|
$20,156
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs