Assessment Year | 2023 |
---|---|
Principal Product | Paper (liner, board, and medium), pulp |
NAICS | 322121: Paper (except Newsprint) Mills |
SIC | 2631: Paperboard Mills |
Sales Range | $50 M to 100M |
# of Employees | 317 |
Plant Area |
700,000
ft2
|
Annual Production | 300,000
ton
|
Production Hrs. Annual | 8,592
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $3,585,004 | 80,984,000 |
kWh
|
$0.044 |
Electricity Demand | $239,476 | 21,148 |
kW-mo/yr
|
$11.32 |
Electricity Fees | $(-528,220.0) | - |
|
- |
TOTAL YEARLY COSTS | $3,296,260 | |||
RECOMMENDED SAVINGS* | $184,017 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $183,786 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $28,885 | - |
$21,282
480,722
kWh
|
$7,603
-
kW-mo/yr
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $5,854 | $372 |
$4,313
97,432
kWh
|
$1,541
-
kW-mo/yr
|
- | |
03 | 2.4226: Use / purchase optimum sized compressor | $148,199 | $381,066 |
$33,177
748,915
kWh
|
$11,822
-
kW-mo/yr
|
$103,200 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $848 | $937 |
$625
14,114
kWh
|
$223
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $231 | $332 |
$231
5,234
kWh
|
- | - | |
TOTAL RECOMMENDED | $184,017 | $382,707 |
$59,628
1,346,417
kWh
|
$21,189
-
kW-mo/yr
|
$103,200 | ||
TOTAL IMPLEMENTED | $183,786 | $382,375 |
$59,397
1,341,183
kWh
|
$21,189
-
kW-mo/yr
|
$103,200 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs