| Assessment Year | 2026 |
|---|---|
| Principal Product | Pullups |
| NAICS | 322291: Sanitary Paper Product Manufacturing |
| SIC | 2676: Sanitary Paper Products |
| Sales Range | $100 M to 500M |
| # of Employees | 500 |
| Plant Area |
1,300,000
ft2
|
| Annual Production | 20,000,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $775,663 | 23,665,920 |
kWh
|
$0.033 | |
| Electricity Demand | $664,471 | 41,844 |
kW-mo/yr
|
$15.88 | |
| Electricity Fees | $479,162 | - |
|
- | |
| Natural Gas | $168,469 | 24,145 |
MMBtu
|
$6.98 | |
| Waste Disposal Costs | |||||
| Water Usage | $45,081 | 14,714 |
Tgal
|
$3.06 | |
| TOTAL YEARLY COSTS | $2,132,846 | ||||
| RECOMMENDED SAVINGS* | $127,976 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2623: Minimize condenser cooling water temperature | $8,440 | $18,000 |
$8,440
257,342
kWh
|
- | |
| 02 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $66,600 | $177,600 |
$5,600
169,800
kWh
|
$61,000
-
MMBtu
|
|
| 03 | 2.7135: Install occupancy sensors | $6,228 | $12,600 |
$6,228
185,523
kWh
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $46,708 | $314,394 |
$46,708
1,424,040
kWh
|
- | |
| TOTAL RECOMMENDED | $127,976 | $522,594 |
$66,976
2,036,705
kWh
|
$61,000
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs