| Assessment Year | 2026 |
|---|---|
| Principal Product | Diapers |
| NAICS | 322291: Sanitary Paper Product Manufacturing |
| SIC | 2676: Sanitary Paper Products |
| Sales Range | $100 M to 500M |
| # of Employees | 500 |
| Plant Area |
1,300,000
ft2
|
| Annual Production | 55,000,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,167,375 | 35,646,792 |
kWh
|
$0.033 |
| Electricity Demand | $1,000,029 | 63,027 |
kW-mo/yr
|
$15.87 |
| Electricity Fees | $721,137 | - |
|
- |
| Natural Gas | $253,546 | 66,562 |
MMBtu
|
$3.81 |
| TOTAL YEARLY COSTS | $3,142,087 | |||
| RECOMMENDED SAVINGS* | $1,016,340 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2625: Chill water to the highest temperature possible | $87,700 | $282,000 |
$32,700
1,000,000
kWh
|
$55,000
-
kW-mo/yr
|
- | |
| 02 | 2.3141: Use battery storage for demand control | $164,000 | $672,400 | - |
$164,000
-
kW-mo/yr
|
- | |
| 03 | 2.4226: Use / purchase optimum sized compressor | $51,100 | $441,000 |
$37,600
1,150,000
kWh
|
$13,500
-
kW-mo/yr
|
- | |
| 04 | 2.4239: Eliminate or reduce compressed air usage | $10,800 | $19,440 |
$10,800
329,000
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,700 | $11,400 |
$11,083
339,000
kWh
|
$7,617
-
kW-mo/yr
|
- | |
| 06 | 2.7273: Install desiccant humidity control system | $86,700 | $86,700 |
$14,061
430,000
kWh
|
- |
$72,639
-
MMBtu
|
|
| 07 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $4,360 | $9,520 | - | - |
$4,360
-
MMBtu
|
|
| 08 | 2.7135: Install occupancy sensors | $3,980 | $27,440 |
$2,914
89,000
kWh
|
$1,066
-
kW-mo/yr
|
- | |
| 09 | 2.9114: Use solar heat to make electricty | $589,000 | $19,489,000 |
$493,770
15,100,000
kWh
|
$95,230
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $1,016,340 | $21,038,900 |
$602,928
18,437,000
kWh
|
$336,413
-
kW-mo/yr
|
$76,999
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs