| Assessment Year | 2025 |
|---|---|
| Principal Product | structural metal bridge supports |
| NAICS | 332312: Fabricated Structural Metal Manufacturing |
| SIC | 3441: Fabricated Structural Metal |
| Sales Range | $10 M to 50M |
| # of Employees | 80 |
| Plant Area |
110,000
ft2
|
| Annual Production | 320
units
|
| Production Hrs. Annual | 4,800
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $84,659 | 2,363,120 |
kWh
|
$0.036 |
| Electricity Demand | $142,813 | 8,790 |
kW-mo/yr
|
$16.25 |
| Electricity Fees | $60,268 | - |
|
- |
| Natural Gas | $47,910 | 3,856 |
MMBtu
|
$12.42 |
| LPG | $180,955 | 8,234 |
MMBtu
|
$21.98 |
| TOTAL YEARLY COSTS | $516,605 | |||
| RECOMMENDED SAVINGS* | $107,112 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $45,761 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $15,681 | $22,500 | - | - |
$(-81,976.0)
-
MMBtu
|
$97,657
-
MMBtu
|
- | |
| 02 | 2.7231: Use radiant heater for spot heating | $8,217 | $13,000 | - | - |
$(-2,643.0)
-
MMBtu
|
$10,860
-
MMBtu
|
- | |
| 03 | 2.1321: Replace fossil fuel equipment with electrical equipment | $52,801 | $18,500 |
$(-24.0)
(-670)
kWh
|
- | - |
$65,158
-
MMBtu
|
$(-12,333.0) | |
| 04 | 2.4226: Use / purchase optimum sized compressor | $15,500 | $38,200 |
$7,500
208,500
kWh
|
$8,000
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $5,730 | $6,960 |
$5,730
160,190
kWh
|
- | - | - | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $633 | $543 |
$633
17,690
kWh
|
- | - | - | - | |
| 07 | 2.3212: Optimize plant power factor | $8,550 | $22,000 | - |
$8,550
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $107,112 | $121,703 |
$13,839
385,710
kWh
|
$16,550
-
kW-mo/yr
|
$(-84,619.0)
-
MMBtu
|
$173,675
-
MMBtu
|
$(-12,333.0) | ||
| TOTAL IMPLEMENTED | $45,761 | $81,203 |
$13,863
386,380
kWh
|
$8,000
-
kW-mo/yr
|
$(-84,619.0)
-
MMBtu
|
$108,517
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs