Assessment Year | 2025 |
---|---|
Principal Product | mashed potatoes, dehydrated potatoes, hash browns, and other flavored potato products |
NAICS | 311423: Dried and Dehydrated Food Manufacturing |
SIC | 2034: Dried and Dehydrated Fruits, Vegetables, and Soup Mixes |
Sales Range | $100 M to 500M |
# of Employees | 350 |
Plant Area |
350,000
ft2
|
Annual Production | 75,000,000
lb
|
Production Hrs. Annual | 7,680
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $990,583 | 17,755,813 |
kWh
|
$0.056 |
Electricity Demand | $330,810 | 25,738 |
kW-mo/yr
|
$12.85 |
Electricity Fees | $41,473 | - |
|
- |
Natural Gas | $4,144,422 | 750,434 |
MMBtu
|
$5.52 |
LPG | $83,132 | 4,169 |
MMBtu
|
$19.94 |
TOTAL YEARLY COSTS | $5,590,420 | |||
RECOMMENDED SAVINGS* | $1,503,560 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.443: Install automatic boiler fuel feed system | $79,422 | $143,652 | - | - |
$79,422
-
MMBtu
|
- | - | |
02 | 2.2441: Preheat boiler makeup water with waste process heat | $215,672 | $730,950 | - | - |
$215,672
-
MMBtu
|
- | - | |
03 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $729,671 | $3,645,455 |
$1,295,464
16,868,021
kWh
|
- |
$(-395,905.0)
-
MMBtu
|
- | $(-169,888.0) | |
04 | 2.1224: Replace boiler | $379,077 | $4,080,441 | - | - |
$379,077
-
MMBtu
|
- | - | |
05 | 2.4224: Upgrade controls on compressors | $3,332 | $4,000 |
$2,823
50,602
kWh
|
$509
-
kW-mo/yr
|
- | - | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $1,905 | $7,317 |
$1,905
34,152
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,405 | $8,915 |
$3,032
54,346
kWh
|
$1,373
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $538 | $1,531 |
$405
7,253
kWh
|
$133
-
kW-mo/yr
|
- | - | - | |
09 | 2.9114: Use solar heat to make electricty | $44,517 | $717,537 |
$44,159
791,540
kWh
|
$358
-
kW-mo/yr
|
- | - | - | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $515 | $916 |
$515
9,227
kWh
|
- | - | - | - | |
11 | 2.1321: Replace fossil fuel equipment with electrical equipment | $44,506 | $432,000 |
$(-32,734.2)
(-586,752)
kWh
|
$(-5,891.8)
-
kW-mo/yr
|
- |
$83,132
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $1,503,560 | $9,772,714 |
$1,315,569
17,228,389
kWh
|
$(-3,519.3)
-
kW-mo/yr
|
$278,266
-
MMBtu
|
$83,132
-
MMBtu
|
$(-169,888.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs