Assessment Year | 2024 |
---|---|
Principal Product | Vitamins and supplements |
NAICS | 325411: Medicinal and Botanical Manufacturing |
SIC | 2833: Medicinal Chemicals and Botanical Products |
Sales Range | $10 M to 50M |
# of Employees | 181 |
Plant Area |
175,000
ft2
|
Annual Production | 30,000,000
units
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $156,103 | 4,850,760 |
kWh
|
$0.032 |
Electricity Demand | $120,818 | 11,506 |
kW-mo/yr
|
$10.50 |
Electricity Fees | $18,638 | - |
|
- |
Natural Gas | $243,318 | 21,261 |
MMBtu
|
$11.44 |
TOTAL YEARLY COSTS | $538,876 | |||
RECOMMENDED SAVINGS* | $99,033 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8113: Purchase gas directly from a contract gas supplier | $64,548 | $8,000 | - | - | - | $64,548 | |
02 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $5,674 | $8,711 | - | - |
$5,674
-
MMBtu
|
- | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,299 | $2,614 | - | - |
$2,299
-
MMBtu
|
- | |
04 | 2.2515: Use optimum thickness insulation | $10,948 | $4,085 | - | - |
$10,948
-
MMBtu
|
- | |
05 | 2.7135: Install occupancy sensors | $1,750 | $4,964 |
$926
28,900
kWh
|
$824
-
kW-mo/yr
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,033 | $8,000 |
$1,327
41,132
kWh
|
$706
-
kW-mo/yr
|
- | - | |
07 | 2.6218: Turn off equipment when not in use | $4,849 | $4,680 |
$4,849
150,586
kWh
|
- | - | - | |
08 | 2.4226: Use / purchase optimum sized compressor | $6,932 | $60,862 |
$4,513
140,255
kWh
|
$2,419
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $99,033 | $101,916 |
$11,615
360,873
kWh
|
$3,949
-
kW-mo/yr
|
$18,921
-
MMBtu
|
$64,548 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs