Assessment Year | 2023 |
---|---|
Principal Product | Aerospace Structural Components |
NAICS | 334511: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical System and Instrument Manufactur |
SIC | 3812: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical Systems and Instruments |
Sales Range | $10 M to 50M |
# of Employees | 227 |
Plant Area |
153,616
ft2
|
Annual Production | 9,000
units
|
Production Hrs. Annual | 6,300
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $63,435 | 1,763,468 |
kWh
|
$0.036 |
Electricity Demand | $84,608 | 5,014 |
kW-mo/yr
|
$16.87 |
Electricity Fees | $19,495 | - |
|
- |
Natural Gas | $129,387 | 13,094 |
MMBtu
|
$9.88 |
TOTAL YEARLY COSTS | $296,925 | |||
RECOMMENDED SAVINGS* | $37,699 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,939 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2691: Shut off cooling if cold outside air will cool process | $13,760 | $120,564 |
$4,648
129,123
kWh
|
$9,112
-
kW-mo/yr
|
- | - | |
02 | 2.1223: Install smaller boiler (increase high fire duty cycle) | $4,878 | $48,510 | - | - | - |
$4,878
-
MMBtu
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,368 | $27,177 |
$3,044
84,320
kWh
|
$3,324
-
kW-mo/yr
|
- | - | |
04 | 2.4226: Use / purchase optimum sized compressor | $5,775 | $52,882 |
$2,653
73,704
kWh
|
$3,122
-
kW-mo/yr
|
- | - | |
05 | 2.3212: Optimize plant power factor | $3,212 | $5,850 | - | - | $3,212 | - | |
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,565 | $1,563 |
$2,565
71,252
kWh
|
- | - | - | |
07 | 2.5194: Redesign process | $913 | $2,360 |
$334
9,277
kWh
|
$579
-
kW-mo/yr
|
- | - | |
08 | 2.2511: Insulate bare equipment | $228 | $1,725 |
$132
3,670
kWh
|
$96
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $37,699 | $260,631 |
$13,376
371,346
kWh
|
$16,233
-
kW-mo/yr
|
$3,212 |
$4,878
-
MMBtu
|
||
TOTAL IMPLEMENTED | $23,939 | $140,067 |
$8,728
242,223
kWh
|
$7,121
-
kW-mo/yr
|
$3,212 |
$4,878
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs