Assessment Year | 2019 |
---|---|
Principal Product | bulk powder capsules |
NAICS | 325411: Medicinal and Botanical Manufacturing |
SIC | 2833: Medicinal Chemicals and Botanical Products |
Sales Range | $50 M to 100M |
# of Employees | 70 |
Plant Area |
48,000
ft2
|
Annual Production | 300,000,000
units
|
Production Hrs. Annual | 4,030
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $36,661 | 1,002,480 |
kWh
|
$0.037 |
Electricity Demand | $47,777 | 2,861 |
kW-mo/yr
|
$16.70 |
Electricity Fees | $7,951 | - |
|
- |
Natural Gas | $9,862 | 1,224 |
MMBtu
|
$8.06 |
TOTAL YEARLY COSTS | $102,251 | |||
RECOMMENDED SAVINGS* | $20,411 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,874 | $9,432 |
$1,758
48,051
kWh
|
$4,116
-
kW-mo/yr
|
- | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $5,611 | $1,000 | - | - | $5,611 | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,173 | $120 |
$690
18,640
kWh
|
$1,483
-
kW-mo/yr
|
- | - | |
04 | 2.3132: Recharge batteries on during off-peak demand periods | $1,980 | - | - |
$1,980
-
kW-mo/yr
|
- | - | |
05 | 2.7224: Reduce space conditioning during non-working hours | $1,945 | $200 |
$859
23,200
kWh
|
- | - |
$1,086
-
MMBtu
|
|
06 | 2.6231: Utilize controls to operate equipment only when needed | $824 | $1,208 |
$507
13,862
kWh
|
$317
-
kW-mo/yr
|
- | - | |
07 | 2.4234: Cool compressor air intake with heat exchanger | $797 | $1,990 |
$304
8,300
kWh
|
$493
-
kW-mo/yr
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $495 | $286 |
$210
5,740
kWh
|
$285
-
kW-mo/yr
|
- | - | |
09 | 2.6231: Utilize controls to operate equipment only when needed | $391 | $300 |
$391
10,693
kWh
|
- | - | - | |
10 | 2.7135: Install occupancy sensors | $322 | $402 |
$322
8,808
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $20,411 | $14,938 |
$5,041
137,294
kWh
|
$8,673
-
kW-mo/yr
|
$5,611 |
$1,086
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs