| Assessment Year | 2019 |
|---|---|
| Principal Product | Treated Water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 4941: Water Supply |
| Sales Range | $5 M to 10M |
| # of Employees | 180 |
| Plant Area |
250,000
ft2
|
| Annual Production | 5,050,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,417,659 | 38,931,709 |
kWh
|
$0.062 |
| TOTAL YEARLY COSTS | $2,417,659 | |||
| RECOMMENDED SAVINGS* | $738,140 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $330,340 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|
| 01 | 3.2161: Closely monitor chemical additions to increase bath life | $377,727 | $30 | - | $377,727 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $176,898 | $256,282 |
$179,374
2,888,469
kWh
|
$(-2,476.0) | |
| 03 | 2.2611: Moderate cooling tower outlet temperature | $149,664 | $22,400 |
$149,664
2,410,048
kWh
|
- | |
| 04 | 2.4226: Use / purchase optimum sized compressor | $30,073 | - |
$30,073
484,280
kWh
|
- | |
| 05 | 2.7135: Install occupancy sensors | $3,778 | $1,225 |
$3,778
60,831
kWh
|
- | |
| TOTAL RECOMMENDED | $738,140 | $279,937 |
$362,889
5,843,628
kWh
|
$375,251 | ||
| TOTAL IMPLEMENTED | $330,340 | $279,907 |
$332,816
5,359,348
kWh
|
$(-2,476.0) | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs