Assessment Year | 2018 |
---|---|
Principal Product | Air bags, seat belts |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 160 |
Plant Area |
165,000
ft2
|
Annual Production | 7,000
units
|
Production Hrs. Annual | 4,437
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $68,825 | 1,886,400 |
kWh
|
$0.036 |
Electricity Demand | $68,399 | 4,109 |
kW-mo/yr
|
$16.65 |
Electricity Fees | $15,608 | - |
|
- |
Natural Gas | $6,704 | 1,007 |
MMBtu
|
$6.66 |
TOTAL YEARLY COSTS | $159,536 | |||
RECOMMENDED SAVINGS* | $53,338 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $42,011 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,322 | $36,216 |
$9,543
261,570
kWh
|
$11,779
-
kW-mo/yr
|
- | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $11,946 | $600 | - | - | $11,946 | - | |
03 | 2.7131: Add area lighting switches | $5,976 | $7,600 |
$2,675
73,317
kWh
|
$3,301
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,897 | $1,428 |
$3,079
84,392
kWh
|
$1,818
-
kW-mo/yr
|
- | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $2,767 | - |
$2,767
75,850
kWh
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $2,708 | $3,750 |
$1,212
33,230
kWh
|
$1,496
-
kW-mo/yr
|
- | - | |
07 | 2.7224: Reduce space conditioning during non-working hours | $1,935 | - |
$1,411
38,669
kWh
|
- | - |
$524
-
MMBtu
|
|
08 | 2.4221: Install compressor air intakes in coolest locations | $1,203 | - |
$740
20,271
kWh
|
$464
-
kW-mo/yr
|
- | - | |
09 | 2.7225: Close outdoor air dampers during warm-up / cool-down periods | $584 | - |
$365
10,015
kWh
|
- | - |
$219
-
MMBtu
|
|
TOTAL RECOMMENDED | $53,338 | $49,594 |
$21,793
597,314
kWh
|
$18,857
-
kW-mo/yr
|
$11,946 |
$742
-
MMBtu
|
||
TOTAL IMPLEMENTED | $42,011 | $44,416 |
$14,986
410,737
kWh
|
$15,080
-
kW-mo/yr
|
$11,946 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |