Assessment Year | 2018 |
---|---|
Principal Product | Marketing Material, Commercial Printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $5 M to 10M |
# of Employees | 100 |
Plant Area |
50,000
ft2
|
Annual Production | 1,000
units
|
Production Hrs. Annual | 3,060
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $86,897 | 945,000 |
kWh
|
$0.092 |
Electricity Demand | $19,983 | 3,278 |
kW-mo/yr
|
$6.10 |
Electricity Fees | $475 | - |
|
- |
TOTAL YEARLY COSTS | $107,355 | |||
RECOMMENDED SAVINGS* | $18,087 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,516 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $7,381 | $29,400 |
$5,803
63,077
kWh
|
$1,578
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,940 | $20 |
$4,543
47,254
kWh
|
$397
-
kW-mo/yr
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,195 | $8,487 |
$2,472
27,471
kWh
|
$723
-
kW-mo/yr
|
|
04 | 2.7135: Install occupancy sensors | $1,822 | $2,775 |
$1,822
19,803
kWh
|
- | |
05 | 2.6232: Install set-back timers | $749 | $675 |
$749
8,143
kWh
|
- | |
TOTAL RECOMMENDED | $18,087 | $41,357 |
$15,389
165,748
kWh
|
$2,698
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $15,516 | $37,907 |
$12,818
137,802
kWh
|
$2,698
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs