Assessment Year | 2017 |
---|---|
Principal Product | NA |
NAICS | 712130: Zoos and Botanical Gardens |
SIC | 7999: Amusement and Recreation Services, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
1,873,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 3,150
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $141,778 | 3,341,177 |
kWh
|
$0.042 | |
Electricity Demand | $97,338 | 9,007 |
kW-mo/yr
|
$10.81 | |
Electricity Fees | $137,517 | - |
|
- | |
Natural Gas | $119,929 | 40,406 |
MMBtu
|
$2.97 | |
Waste Disposal Costs | |||||
Water Usage | $69,908 | 338,673 |
Tgal
|
$0.21 | |
TOTAL YEARLY COSTS | $566,469 | ||||
RECOMMENDED SAVINGS* | $30,703 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $20,848 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $12,503 | - | - |
$9,796
-
kW-mo/yr
|
$2,707 | - | |
02 | 2.3212: Optimize plant power factor | $5,444 | $5,000 | - | - | $5,444 | - | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $4,630 | $3,140 |
$1,920
45,386
kWh
|
$2,537
-
kW-mo/yr
|
$832 |
$(-659.7)
-
MMBtu
|
|
04 | 2.7423: Reduce heat gain by window tinting | $3,392 | $10,800 |
$2,329
55,066
kWh
|
$801
-
kW-mo/yr
|
$263 | - | |
05 | 2.2622: Replace existing chiller with high efficiency model | $1,833 | $4,266 |
$1,335
31,554
kWh
|
$375
-
kW-mo/yr
|
$123 | - | |
06 | 2.6218: Turn off equipment when not in use | $980 | - | - | - | - |
$980
-
MMBtu
|
|
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $854 | $1,702 |
$178
4,217
kWh
|
$200
-
kW-mo/yr
|
$65 |
$410
-
MMBtu
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $681 | $1,463 |
$263
6,214
kWh
|
$315
-
kW-mo/yr
|
$103 | - | |
09 | 2.7224: Reduce space conditioning during non-working hours | $386 | - |
$333
7,868
kWh
|
- | - |
$53
-
MMBtu
|
|
TOTAL RECOMMENDED | $30,703 | $26,371 |
$6,358
150,305
kWh
|
$14,023
-
kW-mo/yr
|
$9,538 |
$784
-
MMBtu
|
||
TOTAL IMPLEMENTED | $20,848 | $8,165 |
$774
18,299
kWh
|
$10,310
-
kW-mo/yr
|
$8,320 |
$1,444
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs