Assessment Year | 2006 |
---|---|
Principal Product | Aluminum Parts |
NAICS | 331318: Other Aluminum Rolling, Drawing, and Extruding |
SIC | 3354: Aluminum Extruded Products |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
363,800
ft2
|
Annual Production | 14,000,000
lb
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $64,500 | 958,680 |
kWh
|
$0.067 |
Electricity Demand | $70,951 | 6,740 |
kW-mo/yr
|
$10.53 |
Natural Gas | $327,108 | 43,052 |
MMBtu
|
$7.60 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $123,630 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $114,100 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $88,420 | $3,500 |
$2,020
72,770
kWh
|
- | - | $86,400 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,430 | $4,040 |
$1,230
44,070
kWh
|
$1,200
-
kW-mo/yr
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $540 | $620 |
$370
13,390
kWh
|
$170
-
kW-mo/yr
|
- | - | |
04 | 2.2511: Insulate bare equipment | $23,250 | $8,290 | - | - |
$23,250
-
MMBtu
|
- | |
05 | 2.4133: Use most efficient type of electric motors | $8,990 | $78,390 |
$4,590
165,000
kWh
|
$4,400
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $123,630 | $94,840 |
$8,210
295,230
kWh
|
$5,770
-
kW-mo/yr
|
$23,250
-
MMBtu
|
$86,400 | ||
TOTAL IMPLEMENTED | $114,100 | $15,830 |
$3,250
116,840
kWh
|
$1,200
-
kW-mo/yr
|
$23,250
-
MMBtu
|
$86,400 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs