Assessment Year | 2003 |
---|---|
Principal Product | stainless steel pieces |
NAICS | 332323: Ornamental and Architectural Metal Work Manufacturing |
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
48,000
ft2
|
Annual Production | 0
pieces
|
Production Hrs. Annual | 2,416
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $24,038 | 516,424 |
kWh
|
$0.047 |
Electricity Demand | $5,165 | 2,014 |
kW-mo/yr
|
$2.56 |
Electricity Fees | $1,293 | - |
|
- |
Natural Gas | $14,495 | 26,275 |
MMBtu
|
$0.55 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,427 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $679 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $335 | $1,600 |
$(-21.0)
(-600)
kWh
|
$(-4.0)
-
kW-mo/yr
|
$360
-
MMBtu
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $325 | $121 |
$270
8,100
kWh
|
$55
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $244 | $58 |
$181
5,500
kWh
|
$63
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $223 | $136 |
$165
5,000
kWh
|
$58
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $190 | $266 |
$134
4,100
kWh
|
$56
-
kW-mo/yr
|
- | |
06 | 2.2437: Recover waste heat from equipment | $110 | $490 | - | - |
$110
-
MMBtu
|
|
TOTAL RECOMMENDED | $1,427 | $2,671 |
$729
22,100
kWh
|
$228
-
kW-mo/yr
|
$470
-
MMBtu
|
||
TOTAL IMPLEMENTED | $679 | $669 |
$451
13,600
kWh
|
$118
-
kW-mo/yr
|
$110
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs