Assessment Year | 2003 |
---|---|
Principal Product | Day planner, paper products |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 68 |
Plant Area |
100,000
ft2
|
Annual Production | 9,850,000
pieces
|
Production Hrs. Annual | 4,992
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $248,144 | 8,946,320 |
kWh
|
$0.028 |
Electricity Demand | $209,986 | 22,544 |
kW-mo/yr
|
$9.31 |
Electricity Fees | $61,515 | - |
|
- |
Natural Gas | $23,321 | 4,283 |
MMBtu
|
$5.45 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,624 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $12,731 | $22,600 | n/a | - | - | $12,731 | - | - |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,035 | $134 | n/a |
$2,793
86,025
kWh
|
$2,242
-
kW-mo/yr
|
- | - | - |
03 | 2.2437: Recover waste heat from equipment | $3,186 | $2,810 | n/a |
$1,412
43,505
kWh
|
$1,142
-
kW-mo/yr
|
- |
$632
-
MMBtu
|
- |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,302 | $1,661 | n/a |
$740
24,283
kWh
|
$562
-
kW-mo/yr
|
- | - | - |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $3,027 | $6,000 | n/a |
$(-74.0)
(-2,295)
kWh
|
$(-41.0)
-
kW-mo/yr
|
- |
$3,142
-
MMBtu
|
- |
06 | 2.7144: Install spectral reflectors / delamp | $2,237 | $410 | n/a |
$835
25,771
kWh
|
$1,402
-
kW-mo/yr
|
- | - | - |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $392 | $594 | n/a |
$213
6,556
kWh
|
$179
-
kW-mo/yr
|
- | - | - |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,664 | $3,366 | n/a |
$2,152
70,705
kWh
|
$1,512
-
kW-mo/yr
|
- | - | - |
09 | 3.5311: Recover and reuse waste material | $50 | - | n/a | - | - | - | - |
$50
-
lb
|
TOTAL RECOMMENDED | $31,624 | $37,575 |
$8,071
254,550
kWh
|
$6,998
-
kW-mo/yr
|
$12,731 |
$3,774
-
MMBtu
|
$50
-
lb
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs