Assessment Year | 2003 |
---|---|
Principal Product | safes |
NAICS |
n/a
|
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
20,400
ft2
|
Annual Production | 50,000
pieces
|
Production Hrs. Annual | 5,200
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $331,989 | 3,883,200 |
kWh
|
$0.085 |
Natural Gas | $95,177 | 19,569 |
MMBtu
|
$4.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $33,073 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,673 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $1,172 | $948 |
$822
19,571
kWh
|
$350
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,938 | $4,181 |
$2,672
63,698
kWh
|
$1,266
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,673 | $190 |
$1,172
27,933
kWh
|
$501
-
kW-mo/yr
|
- | - | |
04 | 4.111: Add equipment/ operators to reduce production bottleneck | $710 | $600 |
$161
3,840
kWh
|
$549
-
kW-mo/yr
|
- | - | |
05 | 2.7145: Install skylights | $11,724 | $16,000 |
$6,330
167,556
kWh
|
$5,394
-
kW-mo/yr
|
- | - | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $12,359 | $600 |
$6,036
143,783
kWh
|
$3,343
-
kW-mo/yr
|
$2,980
-
MMBtu
|
- | |
07 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $897 | $4,226 | - | - |
$897
-
MMBtu
|
- | |
08 | 3.1161: Eliminate/reduce an operation | $600 | $500 | - | - | - | $600 | |
TOTAL RECOMMENDED | $33,073 | $27,245 |
$17,193
426,381
kWh
|
$11,403
-
kW-mo/yr
|
$3,877
-
MMBtu
|
$600 | ||
TOTAL IMPLEMENTED | $1,673 | $190 |
$1,172
27,933
kWh
|
$501
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs