Assessment Year | 2002 |
---|---|
Principal Product | boxes |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $1 M to 5M |
# of Employees | 38 |
Plant Area |
35,000
ft2
|
Annual Production | 29,000
thousand feet
|
Production Hrs. Annual | 2,625
hrs
|
Location (State) | Utah |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $5,861 | 215,520 |
kWh
|
$0.027 |
Electricity Demand | $9,653 | 1,032 |
kW-mo/yr
|
$9.35 |
Electricity Fees | $3,264 | - |
|
- |
Natural Gas | $8,004 | 1,326 |
MMBtu
|
$6.04 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,281 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,085 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $1,624 | $1,800 | - |
$1,624
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,250 | $390 |
$460
14,300
kWh
|
$790
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $379 | $240 |
$162
5,027
kWh
|
$217
-
kW-mo/yr
|
- | |
04 | 2.7243: Improve air circulation with destratification fans / other methods | $929 | $200 |
$(-106.0)
(-3,288)
kWh
|
$(-149.0)
-
kW-mo/yr
|
$1,184
-
MMBtu
|
|
05 | 2.4133: Use most efficient type of electric motors | $1,080 | $1,843 |
$454
14,083
kWh
|
$626
-
kW-mo/yr
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $808 | - |
$339
10,490
kWh
|
$469
-
kW-mo/yr
|
- | |
07 | 2.4314: Use synthetic lubricant | $1,211 | $600 |
$508
15,735
kWh
|
$703
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $7,281 | $5,073 |
$1,817
56,347
kWh
|
$4,280
-
kW-mo/yr
|
$1,184
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,085 | $2,790 |
$968
30,035
kWh
|
$3,117
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs