| Assessment Year | 2001 |
|---|---|
| Principal Product | Linen suppliers |
| NAICS |
n/a
|
| SIC | 2389: Apparel and Accessories, Not Elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 50 |
| Plant Area |
15,000
ft2
|
| Annual Production | 5,200,000
lb
|
| Production Hrs. Annual | 4,590
hrs
|
| Location (State) | Utah |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $11,449 | 277,040 |
kWh
|
$0.041 |
| Electricity Demand | $5,719 | 1,236 |
kW-mo/yr
|
$4.63 |
| Electricity Fees | $2,176 | - |
|
- |
| Natural Gas | $92,644 | 14,641 |
MMBtu
|
$6.33 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $17,864 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $173 | $141 |
$100
3,602
kWh
|
$73
-
kW-mo/yr
|
- | |
| 02 | 2.2511: Insulate bare equipment | $422 | $625 | - | - |
$422
-
MMBtu
|
|
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,040 | - |
$673
24,389
kWh
|
$367
-
kW-mo/yr
|
- | |
| 04 | 2.4314: Use synthetic lubricant | $1,715 | $800 |
$1,110
40,199
kWh
|
$605
-
kW-mo/yr
|
- | |
| 05 | 2.4133: Use most efficient type of electric motors | $1,486 | $5,165 |
$843
30,933
kWh
|
$643
-
kW-mo/yr
|
- | |
| 06 | 2.7124: Make a practice of turning off lights when not needed | $839 | - |
$486
17,604
kWh
|
$353
-
kW-mo/yr
|
- | |
| 07 | 2.1116: Improve combustion control capability | $12,189 | $21,500 | - | - |
$12,189
-
MMBtu
|
|
| TOTAL RECOMMENDED | $17,864 | $28,231 |
$3,212
116,727
kWh
|
$2,041
-
kW-mo/yr
|
$12,611
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs