| Assessment Year | 2017 |
|---|---|
| Principal Product | Aquence Coating and VAA |
| NAICS | 335312: Motor and Generator Manufacturing |
| SIC | 3621: Motors and Generators |
| Sales Range | $10 M to 50M |
| # of Employees | 125 |
| Plant Area |
460,000
ft2
|
| Annual Production | 1,000,000
pieces
|
| Production Hrs. Annual | 5,640
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $467,060 | 4,652,000 |
kWh
|
$0.10 |
| Electricity Demand | $111,090 | 10,640 |
kW-mo/yr
|
$10.44 |
| Natural Gas | $265,266 | 55,451 |
MMBtu
|
$4.78 |
| TOTAL YEARLY COSTS | $843,416 | |||
| RECOMMENDED SAVINGS* | $69,037 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $3,265 | $4,500 |
$3,265
32,653
kWh
|
- | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $42,701 | $105,530 |
$30,964
309,636
kWh
|
$6,878
-
kW-mo/yr
|
- | $4,859 | |
| 03 | 2.2514: Cover open tanks | $23,071 | $2,137 | - | - |
$23,071
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $69,037 | $112,167 |
$34,229
342,289
kWh
|
$6,878
-
kW-mo/yr
|
$23,071
-
MMBtu
|
$4,859 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs