Assessment Year | 2002 |
---|---|
Principal Product | manufacturing and filling plastic bottles |
NAICS |
n/a
|
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 274 |
Plant Area |
392,000
ft2
|
Annual Production | 50,000,000
units
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,488,447 | 53,980,895 |
kWh
|
$0.083 |
Electricity Demand | $1,071,759 | 98,544 |
kW-mo/yr
|
$10.88 |
Electricity Fees | $(-1,676,357.0) | - |
|
- |
Natural Gas | $234,664 | 34,491 |
MMBtu
|
$6.80 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $1,298,479 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $897,246 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $203,445 | $95,480 |
$179,698
2,109,631
kWh
|
$23,747
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $2,227 | $1,335 |
$1,993
23,400
kWh
|
$234
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $15,015 | $550 |
$13,662
160,355
kWh
|
$2,135
-
kW-mo/yr
|
- | $(-782.0) | - | - | |
04 | 2.4224: Upgrade controls on compressors | $19,570 | $300 |
$17,685
182,056
kWh
|
$1,885
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4322: Use or replace with energy efficient substitutes | $21,342 | $4,800 |
$15,852
185,835
kWh
|
$5,490
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,928 | $23,600 |
$8,569
100,600
kWh
|
$1,359
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $24,505 | $21,928 |
$26,489
310,980
kWh
|
$3,975
-
kW-mo/yr
|
$(-5,959.0)
-
MMBtu
|
- | - | - | |
08 | 4.642: Install sensors to detect and avoid jams | $101,250 | $15,800 | - | - | - | - | $101,250 | - | |
09 | 4.111: Add equipment/ operators to reduce production bottleneck | $145,152 | $2,000 | - | - | - | - | $145,152 | - | |
10 | 4.652: Replace existing equipment with more suitable substitutes | $202,078 | $453,275 |
$15,299
179,610
kWh
|
$2,394
-
kW-mo/yr
|
- | $5,555 | - | $178,830 | |
11 | 4.652: Replace existing equipment with more suitable substitutes | $199,710 | $14,000 | - | - | - | - | $199,710 | - | |
12 | 4.625: Develop standard operating procedures | $354,257 | $45,500 | - | - | - | - | - | $354,257 | |
TOTAL RECOMMENDED | $1,298,479 | $678,568 |
$279,247
3,252,467
kWh
|
$41,219
-
kW-mo/yr
|
$(-5,959.0)
-
MMBtu
|
$4,773 | $446,112 | $533,087 | ||
TOTAL IMPLEMENTED | $897,246 | $177,465 |
$211,205
2,479,221
kWh
|
$31,606
-
kW-mo/yr
|
- | $(-782.0) | $300,960 | $354,257 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs